UBER

HVAC | Design and Construct of New Open Ceiling AC System with Ductsox as a New Feature
480-Hay-Street1

6-off mid static ducted FCUs spring hanger mounted complete with safety trays under with p trapped drain to nearest tundish. Flexible connections to ductwork. 50mm deep panel filter plenum.

Unit Type Supply Air Outside GTH GTSH Coil entering conditions
l/s l/s kW kW CDB CWB
AC1 Mid Static Ducted 500 70 8.5 6.5 25.8 18.2
AC2 Mid Static Ducted 500 80 8.5 6.5 26.0 18.3
AC3 Mid Static Ducted 530 80 8.5 6.5 25.9 18.2
AC4 Mid Static Ducted 300 80 8.5 6.5 27.4 18.8
AC5 Mid Static Ducted 650 100 11.5 9.5 25.9 18.3
AC6 Mid Static Ducted 500 40 8.5 6.5 25.0 17.9
AC7 Wall Split Cooling Only 220 0 4 3 24.0 17.5

Fans

Roof toilet exhaust system to AS1668.2. Dual fans on VSD. 170L/s @80Pa.

Ducted Fresh air system to supply fresh air to units. Fan on VSD. 450L/s @140Pa. Provide 300mm deep filter plenum on intake. Attenuator in plantroom wall.

All fans on spring hanger mounts with flexible connections to inlet and discharge ductwork. Fantech or equal approved.